Product Description
GROUND LEAKAGE ALARM
Requires Toroidal Current Transformer (such as BZCT-035 or BZCT-070)
Operational Details:
- Utilizes a 120 VAC control in conjunction with the Toroidal Current Transformer.
- Initial power-up activates a green indicator light.
- Ground leakage triggers a red indicator and, if leakage intensifies, an alarm will sound.
Compliance:
- Meets CEC Rule 10-106(2) requirements for underground supply systems, equipped with a device to detect and indicate ground presence.
System Compatibility:
- Compatible with 3Ø Wye, 3Ø Delta, or single-phase systems.
Lamp Specifications:
- Equipped with durable and efficient LED lamps.
Additional Features:
- Includes an auxiliary contact - Form C with AC1 rating: 8A at 250 VAC.
- Microprocessor control allows for customizable parameters.
- Features fault and ready lights, test and reset buttons, and an alarm buzzer.
Enclosure Specifications:
- NEMA 3R rated for outdoor use. Dimensions: 11.875” height, 7.25” width, 4.75” depth.
- Offers customization options for names or contractor branding.